The Eagle Eye Power Solutions LB-125-600-CC LB-Series Constant Current DC Load Tester provides programmable constant current discharge testing for 125V DC battery systems up to 600 amps. Designed for utility substations, telecommunications facilities, UPS systems, industrial DC plants, and other stationary power applications, this model delivers dependable battery capacity verification and performance validation.

The LB-125-600-CC features intelligent constant current technology that maintains the programmed discharge level throughout the test without manual adjustment. Its backlit LED display provides clear visibility of voltage, current, and elapsed test time, ensuring operators have accurate, real-time feedback.

Four programmable discharge auto-stop conditions — including test time, end voltage, exceeded capacity, and cell voltage (when applicable) — enhance test control and safety. Built-in protections automatically stop the discharge in the event of overheating, abnormal battery disconnection, or improper polarity detection.

Features

  • 125V System Testing: Designed for 125V DC battery systems.
  • Up to 600A Constant Current Discharge: Intelligent technology maintains programmed current without manual adjustment.
  • Auto-Sensing Voltage (5–600V Range): Automatically detects system voltage.
  • LED Display: Backlit numeric LED displays voltage, current, and test time.
  • Four Auto-Stop Conditions: Test Time, End Voltage, Exceeded Capacity, and Cell Voltage (CCS models only).
  • Built-In Safety Protections: Stops discharge in cases of overheating, abnormal battery disconnection, or improper polarity.
  • Automatic Fan Cooling: Continues fan operation after testing for enhanced heat protection.
  • Parameter Memory: Saves previously used test settings after power-off.
  • Optional Software Package: Reporting to Excel and Word, data graphs, and remote load control available.

Specifications

Nominal System Voltage:125 VDC
Discharge Voltage Range:5 – 600V (Auto-Sensing)
Discharge Current Range:1 – 600A
Per Cell Voltage Type:1 – 12V VRLA, VLA, NiCad, and similar chemistries
Accuracy:Current: ±1% / Voltage: ±1%
Resolution:Current: 0.1A / Voltage: 0.1V
Data Transfer:RS-232, USB
Display:Backlit Numeric LED (Constant Current Model)
Operating Environment:0 – 40 °C (32 – 104 °F)
Power Requirements:110/220 VAC 50/60 Hz
Dimensions:Varies by enclosure size (Small through XXX-Large)
Weight:Varies by enclosure size (49 – 662 lbs.)

Resources & Support

Videos

FAQs

What battery systems is the Eagle Eye Power Solutions LB-125-600-CC LB-Series Constant Current DC Load Tester designed for?

This model is designed for 125V DC battery systems commonly found in utility substations, telecom sites, UPS systems, and industrial power facilities.

What does constant current technology mean?

The LB-125-600-CC automatically maintains the programmed discharge current throughout the test without requiring manual adjustment.

Can this load tester be used for NERC compliance testing?

Yes. The constant current discharge capability supports capacity verification and documentation requirements for compliance-driven maintenance programs.

What safety protections are built into this unit?

The unit automatically stops discharge in cases of overheating, abnormal battery disconnection, or improper polarity detection. It also includes programmable discharge auto-stop conditions.

Can I export test results?

Optional software packages allow reporting to Microsoft Excel and Word, data graphing, and remote load control.

Does this unit support cell monitoring?

Cell voltage monitoring is available on CCS models and select optional configurations.

Ratings & Reviews